I have created LD diagram according to this link 

openplc_temsensor.png 

So here i want to map temperature sensor value to modbus simulator's input register and same way wants to show status of lamp in coil register.I have tried with some simulator not able to see the value inside run time monitoring web browser .Is there any modbus simulator available which is compatible to openplc .Please provide that information.
Quote 0 0
thiagoralves

Modbus is a standard protocol. Any modbus slave (server) simulator should work with OpenPLC if you set it properly. 2 minutes of Google-Fu brought me this:
https://sourceforge.net/projects/modrssim2/

and this:

https://www.modbustools.com/modbus_slave.html

Just setup any of those on your computer, and then add a new slave device on OpenPLC (Generic Modbus TCP). Make sure you set the parameters properly (IP address, port, number of coils, etc)

Quote 0 0
joydip
Thanks for your quick response.I have tried with Modbus pal simulator,I have attached screenshot.I did register mapping with simulator and ran simulator, still not getting data in openplc run time,Please check screenshot and please suggest me what i am missing.
 
Quote 0 0
thiagoralves
Have you added a slave device pointing to your simulator as I said in the previous post? I didn’t see any screenshot of your slave device configuration on the runtime. Also, slave devices attach to address 100 and up, so your variables should be something like %QX100.0 and %IW100
Quote 0 0
joydip
Thanks for your help,Now it is working.Now i am able to see output coil value is changing depending upon input value on modbus simulator,
But one problem still facing values are not updating on openplc web browser Monitoring page,can you please help me on that.
Quote 0 0
thiagoralves
Is OpenPLC runtime running on the same computer as your Modbus simulator? If so, you gotta change the port on the simulator because if it is using port 502 it will conflict with OpenPLC and that’s probably why Monitoring is not working
Quote 0 0