Hello, at the documentation in the addressing page here https://www.openplcproject.com/reference/modbus/ , don't understand the part talking about Input Addresses and Holding Registers.  Screenshot 2020-07-22 at 17.09.58.png  In the Coil and Input registers is clear 800 PLC addresses, but in the Input registers and the holding registers there are only 100 but 1024 addresses? the same thing occurs for the other holding registers.
Cant figure out why 
Thanks
Reply 0 0
thiagoralves
That table is incorrect. IW and QW addresses should be up to 1023. The more up to date addressing explanation is here:  https://www.openplcproject.com/reference/modbus-slave/ 
Reply 0 0
arraiz
Thats helpful, thanks! 