I am trying to write a value 1 to location %Qx0.0 using a modbus-write node to openPLC running on RPI. and read the Location %QX0.1 using modbus-read node ( in node-red )  . can someone please help me with the Address i need to fill while configuring the nodes.

Thanks in Advance.

with warm regards.


This is the Program
Screenshot from 2019-01-09 04-40-18.png 
Node-red flow diagram

Screenshot from 2019-01-09 04-10-18.png 
values I need to fill in modbus-write node ?
Screenshot from 2019-01-09 04-10-24.png 
similarly value i need to fill in modbus read node. ?

Screenshot from 2019-01-09 04-10-33.png 
Finally I need the LED light to glow which is connected to pin No %QX0.1 when i press the trigger button in node-red.  

Thanks again for the help



Reply 0 0
thiagoralves
I don't know much about nodeRED, but the modbus address you need to use to access QX0.0 is 0, not 0.0. Modbus addresses don't have the dot notation. You can find the modbus address correlation table here: openplcproject.com/scada
Reply 0 0
noobPLC
Thanks for the help
Reply 0 0
noobPLC
And variable TOF is not appearing on openPLC editor. any idea why its not coming ?
Reply 0 0
thiagoralves
What do you mean by that? TOF is not a variable, it is a timer block. You insert it on the program by right-clicking on the editor and selecting add->block, and then choosing the TOF block
Reply 0 0