Why can't I connect an input contact to TON? It seems like I can only "assign" it when I am in Execution mode and it shows off to the side, but then it doesn't look like standard ladder logic. This is version 4.1.1 on MacOS.
Reply 0 0
thiagoralves
Yes you can connect contacts to blocks. Just drag the contact from the left sidebar and place it before or after the TON block. This will connect the contact to the IN input of the TON block if you place the contact before the block, or to the Q output of the TON block if you place the contact after the block
Reply 0 0
Khuram Ali
Hi I need information about timer TON how to sign bit for hmi (PT)'(ET )control.... In ladder diagram...
Reply 0 0
thiagoralves
ET is an output, so you can't control that, only read. Depending on which HMI and protocol you are using, you can expose these variables directly by using OPC-UA. If using Modbus, then you need to convert both PT and ET to INT before you can expose them to HMIs. Since you haven't provided much detail on what type of HMI, protocol, or project you're working on, I can't tell which approach would be best.
Reply 1 0
Khuram Ali
"Wintek HMI "I need to control time also remains ET display on HMI.i am useing modbus.. Serial communication with Arduino mega..
Reply 0 0
thiagoralves
If you’re using Modbus then you will have to convert the TIME variables to INT using the TIME_TO_INT block and place the INT value on a Modbus location (like %QW for example)
Reply 0 0
Khuram Ali
In ladder diagram also work time to int...?
Reply 0 0
thiagoralves
Yes
Reply 0 0
Khuram Ali
Thanks..
Reply 0 0