azkom
A HMI(Kinco) connected to a PLC(Controllino MEGA). It works fine, using the ModBus TCP protocol between HMI-PLC. I would like to connect an RS485 device to  Controllino MEGA, which has a different address (e.g. 50, PLC  address is 1).
How can I read e.g. holdig registers of the RS485 device with addess 50 by OpenPLC?
 
Reply 0 0
thiagoralves
You can’t. OpenPLC on Controllino only supports Modbus slave mode. It can’t read/write data on other devices
Reply 0 0
azkom
When I set up the comunications, before transfer, I can check both Modbus RTU and Modbus TCP. In case of Modbus RTU I can define a differet address. How can I use the 2 protocols or I can use it only in direction of HMI, the Modbus Master?
Reply 0 0
thiagoralves
You can use both Modbus tcp and RTU at the same time if you want, but as I said, only as a slave. You cannot control other devices 
Reply 0 0
Reply