Hello, I am new to all this. I have Modbus down master/slave talking etc. But if there any info on setting up DNP3? thanks.
Reply 0 0
nOOb
I am not sure how I would add it to the logic, any direction? thanks
Reply 0 0
thiagoralves
OpenPLC doesn't support RTC instructions yet. OpenPLC uses open-dnp3 network stack, and as per their documentation, open-dnp3 stack doesn't support reading Obj 50, as that's outside the level 2 compliance set.
Reply 0 0
nOOb
ah I see. Thanks.
Reply 0 0
ku86755
Hi,thiagoralves:
     I have a similar question,the input coils is OK ,but the output coils looks wrong, It looks like it is causeed by the host of OpenPLC,here's some of the relevant information,could  you take a look for me? 
 
 System: Scada-LTS: v2.6.18 build 3789793762(GitHub ref: db11068);runs on Linux5.4.0-150-generic
1.png
2.png
3.png4.png5.png6.png
7.png
Reply 0 0
thiagoralves
The DNP3 server needs an update. It is running on a very old version of opendnp3 and the code most likely needs to be refactored. Any help on refactoring this will be much appreciated.
Reply 0 0