Josef Bernhardt
Hello everybody,
I have a little problem with the ESP8266 Modbus TCP module.
If I want to read out the status of the coils, it works quite well if I read out four values ​​with start address 1.

Tx: 00 42 00 00 00 06 01 01 00 00 00 04
Rx: 00 42 00 00 00 04 01 01 01 01

If I want to read one value from start address 1, it also works.

Tx: 00 45 00 00 00 06 01 01 00 00 00 01
Rx: 00 45 00 00 00 04 01 01 01 01

But if I want to read one value from start address 2, 3 or 4, I get an error message.

Tx: 00 53 00 00 00 06 01 01 00 01 00 01
Rx: 00 53 00 00 00 03 01 81 02

What could I change in the ESP8266 Arduino software so that the command also reads values ​​from an address greater than 1.

The problem has now appeared with an HMI software for Android (suppanel)

I would like to use the ESP8266 because it is the best implementation for the Modbus that I know.

Maybe someone has an idea how I could solve the problem.

Regards Josef Bernhardt