Hello.
 
I'm taking in and OpenPLC Editor and OpenPLC Runtime.
I'm presently running OpenpPLC Runtime on my PC (Ubuntu)
 
I've been following the blink example program tutorial and it worked well. I mean the Led was virtually blinking in OpenPLC Runtime Monitoring window.
 
I then made this program :
Editor.png
But I can't virtually change the state of the StartSwitch or the StopSwitch :
Runtime.png
 
Despite clinking on StartSwitch that take me to the following screen :
StartSwitch.png
 
 
Here is the setting for the Hardware (Blank Linux) :
Capture d’écran du 2024-03-13 20-44-37.png
 
I hope my explanation are good enough to make my question clear enough.
Reply 0 0
thiagoralves
Forcing variables does not work on the runtime monitoring. It was a planned feature that never got finished. We're now moving to live monitoring (which will come soon to the Linux runtime) so this feature will have no practical use.
 
In the mean time, if you want to force variables, declare them as located outputs (%QX, %QW, %MW range) and then use Modbus tools like Radzio to read/write to them.
Reply 0 0
hary66
Hello Thiago.
I think I've seen you using Radzio in one off your video, but I don't remember which one ?
Would you remember ?
Reply 0 0