JuanDa
It is possible to modify the starting modbus address? I need to start my holding register in the address 1, at the moment I only can start from 1024. I need that the Raspberry pi (slave server) receives the data from a client in the address 1 (I need to write INT values %MW)
 
[203128%2F9714326%2Fmceclip0]
Reply 0 0
PeBi
This input screen defines only the size of the individual Modbus registers.
For example:
If you set the size of the output registers %QW to 10,
the output range %QW0–%QW9 can be used as output variables in the program.
These are then located in the Modbus register range in words 0–9
 
[203128%2F9714468%2Fmceclip0]
 
[203128%2F9714469%2Fmceclip0]
 
[203128%2F9714470%2Fmceclip0]
Reply 0 0
thiagoralves
The %QW location and all %M locations share the same holding registers space. You’re probably using %MW in your program, and from the size configuration, that will be starting on holding register 1024(%MW0 = 1024). If you want to have %MW0 = 1, then set QW size to 1 so that MW starts at holding register 1