Hi ,

I m trying to connect Open PLC with WinCC . I have successfully connected Digital Inputs and outputs of ESP 8266 board. 

What is the modbus adress mapped with %IW100. 

Thanks

Reply 0 0
thiagoralves
Input Register 100
Reply 0 0
Rizwan Ahmed
Thanks Thiagoralves.

One more question.

Is there any possibility monitor ladder logic in realtime.?
Reply 0 0
thiagoralves
Not yet. The monitoring functionality is still in the works. You can use SCADA softwares to read registers in real time, which can work for monitoring as well. 
Reply 0 0
Rizwan Ahmed

I m using Siemens WinCC with Open PLC , Its Working fine. But Diagnostic is very difficult, without online troubleshooting.

Secondly. IP of the slave device (ESP 8266) changes sometime , because of DHCP . How to make the IP of ESP 8266 static.

One more thing. Is it possible to use ESP 8266 as MODBUS TCP Slave  with other devices except OpenPLC ??

Reply 0 0
thiagoralves

Secondly. IP of the slave device (ESP 8266) changes sometime , because of DHCP . How to make the IP of ESP 8266 static.


The easiest way is to configure your router to always give the same IP to your ESP. The other (a bit more complicated) way is to modify the ESP firmware and make it have a fixed IP.

One more thing. Is it possible to use ESP 8266 as MODBUS TCP Slave  with other devices except OpenPLC ??


Yes. The firmware for the ESP is purely a Modbus server.
Reply 0 0