How mapping a the real value to the Modbus address.
I use %md0 of the real value, but I can not find value
with the program modscan.
Quote 0 0
thiagoralves
Right now you can't. I still need to improve modbus mapping, but currently only I/O is mapped to Modbus. So, the first 100 analog outputs (%QW0.0 - %QW0.100) are mapped to Modbus holding registers, and these values are individual 16-bit registers. Analog and digital inputs and coils are also equally mapped.

In the next weeks I will write code to map memory variables to Modbus and update the website with a memory map.
Quote 0 0
thiagoralves
I updated the code for the modbus module and now it supports memory and real values. Check the News & Announcements section for more details [smile]