Dears, I am facing problem with communicating with victron cerbo controller over modbus. Cerbo uses slave ID to differentiate between hardware: Example: MPPT has ID 125, inverter has 100, system has 1 and so on. When slave id configured to 100, from the log we can see the PLC is using dev_id = 1. It seems to be ignoring configured slave id.
 
Runtime 4.1 on raspberry pi4
Editor on Windows 11 PC v 4.1.2
 
Can anyone give me hint how to force the runtime to use configured slave id?
 
Thank you[203128%2F9694544%2Fmceclip0]
I really like PLCs
Reply 0 0
thiagoralves
Make sure you’re using the latest version of the runtime. The slave id on Modbus TCP was added on v4.0.7
Reply 0 0
Yermen
@thiagoralves thank you,
you were right, I made an update but forgot to stop the service. Then the update was somehow corrupt. So stopping service then new instalation did the thing.
 
BR Jan