is there a way i can do a MOVP in open PLC? i have a UINT output variable id like to change based on the state of several BOOL.
Reply 0 0
Tmathews1988
is there a way i can do a MOVP in open PLC? i have a UINT output variable id like to change based on the state of several BOOL.
i tried to do this with a few MOV with a enable then a set variable on the MOV command and pulsed the enable but the other MOV always forced 0 back into my output. 
Reply 0 0
thiagoralves
As long as all your MOV blocks are controlled with an EN pin it should work. Make sure you’re looking at the variable value on the debugger (glasses in front on variable name on left panel) and not just the ladder line
Reply 0 0