David_R
Hello Guys, i found out yesterday that i cant
transfer arrays via OPC UA. Is there a workaround exept to create new variables and assign them to the array variable?
Reply 0 0
thiagoralves
Yes, you can use arrays with OPC-UA:
Screenshot 2026-05-01 at 7.47.28 AM.png
Reply 0 0
David_R
you are right, if im working only with single variables, it works, but if i have for example an Array of User defined datatypes it does not work:
[203128%2F9765307%2Fmceclip0]
Reply 0 0
thiagoralves
That's a bug. Please open a ticket at https://github.com/autonomy-logic/openplc-editor/issues
Reply 0 0
Desire
Hi David_R,
I am interested in this topic.
Can you share how you do UPC UA connection in V4 environment?
Thanks in advance,
Desire
Reply 0 0
David_R
Hi, im doing it with Open PLC and Fuxa
You can simply add the OPC UA Server in your programm with + -> Server -> select OPC UA Server
[203128%2F9770940%2Fmceclip0]
Reply 0 0
Reply