I have a ladder code it work in openplc v3
I cloned the code in V4 and made a c++ code for the PLC model I have KC868-A16
In the code, I have negated contacts who do not seem to pass signal if I force a contact before the "coil" even if it's not activated and should let the signal pass it seems to block. Unless I did something wrong, the behavior seems strange here I force RST_R but x1 is not activated x2 should pass the signal, but it does not [203128%2F9652189%2Fmceclip0][203128%2F9652186%2Fmceclip0]
Reply 0 0
thiagoralves
Add x2 to the debugger (bug icon at the variables table) and check if it is True. My hint is the x2 is true and therefore the negated contact becomes false