Hi,
I am using the P1AM-100 series with limited modbus addresses.  
The P1AM-100 physical addresses are here:
I would expect the physical addresses to be the same? edit -> actually there may be more available as there are no used header pins for extension board communication (See github facts engineering)
 
The P1AM-200 has much more available memory. What are the modbus addresses available with this device?
The available memory based addresses are here for the 100 series:
Outputs: %QX0.0 – %QX6.7
Inputs: %IX0.0 – %IX6.7
I would hope that the 200 series has much larger range? I want to go above the 55 count available on the 100 for my application
Thanks,
Reply 0 0
thiagoralves
OpenPLC defines the same address space for all microcontroller-based platforms. See   https://openplc.discussion.community/post/maxmemoryword-13641755
 
There isn’t a way to modify or expand this without modifying the source code of the runtime and editor.
 
However, this does not mean you’re limited to only using 55 boolean variables. This limit is only on located variables (i.e. variables exported to Modbus). You can still define as many variables as you need without using a location