Hi Thiago, 

recently i want to read the data from other slave devices but i got about 100 or 200 ms delay. I am not sure if the problem comes from OpenPLC or other slave devices. I want to know if it is possible to change the update speed of the buffers which are set by the slave devices?

Thanks! ^_^


Quote 0 0
thiagoralves
Yes. On the OpenPLC Runtime, go to Settings -> Slave Devices -> Polling Period and adjust accordingly. Just keep in mind that a very short period might get your slave devices too busy and overload the bus.
Quote 1 0
zp
Thanks for your advise! ^_^