zhong
Hi, sir.
Has there been any modification to openplc runtime v3? Why does openplc runtime v3 fail to connect when using editor v4.1.0, but the connection succeeds when using editor v3, even though I've entered the same IP address?
Reply 0 0
thiagoralves
The v3 editor does not connect to the v3 runtime. This feature was never added to it. The v3 editor can only connect to debug the runtime. I don’t know what type of connection you’re trying to make from the v4 editor, but it can connect just fine to the v3 runtime. Just make sure you’re running the latest version of the v3 runtime.
Reply 0 0