I see that OpenPLC operates as a modbus slave by default.  Does it need a program/st file to function as a slave, or will it behave properly with no program uploaded?

If no program is needed to function as a slave device, how can you remove a previously uploaded program.

Sorry if I am misunderstanding.  I'd like to try setting up a modbus master like noted on http://www.openplcproject.com/getting-started-modbus-io
Reply 0 0
thiagoralves
OpenPLC will always be a modbus slave, independently of the program it is running. You cannot remove a previously uploaded program since the program is part of the OpenPLC executable. What you can do is to upload a new "dummy" program that does nothing. Just create a program with a single rung (empty programs cannot be uploaded) and with no located variables. You can even get the hello world example from the website and delete the "location" address of the variables (just the location, not the variables). This will make the variables be internal variables and then OpenPLC won't do anything with it.
Reply 1 0