Hello, I am running open PLC runtime V4 on docker (with docker Compose file) and i have issues to connect Fuxa to the PLC.
I have tried it also with Modbus TCP and this works.
I have added screenshots of the configuration. Could anybody help me with this?
 
[203128%2F9758542%2Fmceclip0]
 
[203128%2F9758543%2Fmceclip0]
 
[203128%2F9758544%2Fmceclip0]
Reply 1 0
thiagoralves
You need to put the full OPC-UA path on the address. Check the PLC Logs on the editor when you upload your program. It will print the full OPC-UA path you configured
Reply 0 0
David_R
Hi, thanks for your respone, i don't get it, where can i find the full path?
i only find something like this in my compiling loggs:
[203128%2F9759073%2Fmceclip0]
 
In fuxa, i'll tried a view paths, and configs, but it seems that i havent set it up correctly.... (with the path and without, only IP wit port, etc...)

[203128%2F9759076%2Fmceclip0]
has anybody ever tried it, or knows where i can find the full OPC UA path?
Reply 0 0
thiagoralves
You’re looking at the compilation logs where you should look at the  PLC Logs (the other tab next to Console where the compilation logs are)
Reply 1 0
David_R
OK i see, thanks that worked!
Reply 0 0