Hi,

I have a question related to the asynchronous effect of polling slave's value on the OpenPLC logic.
Is that a design choice or a standard in the industrial PLC?  How does that work with
the scan cycle (feedback loop) where the output should be synchronous with the input?

Thanks,
Reply 0 0
thiagoralves
This was a design choice for OpenPLC, mainly due to the fact that Modbus is not a real time protocol, therefore it would be impossible to guarantee the cyclic effect of the scan time. 
Reply 0 0
Qaseem
Many thanks for the clarification.