I took a better look at your project below and now I understood what is happening. You located your byte values at %MB locations. These locations don't exist on OpenPLC mapping, that's why your values are being displayed as zeros. For the simulation, the compiler strips out all located variables for the debugger, so it doesn't matter what you write in the location field. Remove the location address from your BYTE variables and try again. I'm pretty confident it is going to work just fine.
For debugging purposes, you can always convert back the BYTE to WORD and store it in a %MW register. That can be displayed just fine.
Been banging my head against the wall for ~2 days now, and have come to conclusion that either there's a fundamental error/bug in the Raspberry PI (3B, 64-bit if that matters) implementation of OpenPLC_v3 Runtime, or I'm missing something super basic.
I'm trying to extract the 16-bits from a UINT analog input in a Raspberry PI. The FBD used seems to work until the WORD_TO_BYTE type conversion, then that conversion always returns 0. The weird thing is the exact same FBD, just run within the PLC Simulator inside OpenPLC Editor instead of on the Raspberry PI, works fine.
FBD to Extract 16-bits from a UINT

Details of BYTE_TO_BIT Block:

This test program works perfectly fine in OpenPLC Editor, in the "Start PLC Simulation" mode.

But uploading the *.ST file to a Raspberry PI running OpenPLC_v3 Runtime fails (DEBUG_LSB = 0, DEBUG_MSB = 0, all Bx = FALSE):