JPak
Hello everyone,
i have this problem where my buscoppler BK9000 from Beckhoff does not allow a new ModBus connection after stopping and restarting the plc program.
Beckhoff documentation states that resetting the watchdog register at Point of Connect should allow new connections.
Is this problem already known and / or is there a possible solution for it?
The same problem should exist with wago equivalent buscopplers (Beckhoff and Wago developed them together)

Thanks in advance
Jan
Reply 0 0
mhe
the BK9000 recommended default is "max. tcp connections = 3"

If you connect concurrently with "modbus polling" and other tools or restart OpenPLC too fast then you get "no tcp connection" from BK9000.
This is a standard behaviour with all tcp devices.
Even if you start multiple modbus-clients (master) from one PLC to request a modbus-server (slave) you can run into this problem.

Restart modbus-server (BK9000) and OpenPLC should reset the connections.

To analyse the real network traffic you can use wireshark with modbus filter
Reply 0 0