ericbaylor
First, I am new to SCADA and I think your site is awesome.
Second, I am trying to replicate your DEFCON 26 demo and would like to know the specific gear you used. I heard you used a Allen-Bradley MicroLogic 1400, Uni Pi 1.1, and Modicon. Also you used a temperature sensor that I believe is an add-on to the Uni Pi 1.1. I didn't see your device that heated the water though.

Question: what specific three PLCs did you use, What attachments i.e. heating and sensing devices did you use, and any specific configurations that you applied would also be super helpful.

Thank you for this site and any support on my . . .  your project 🙂
Reply 0 0
thiagoralves
Hi Eric,

Thank you for your message. You can find more information about my DEFCON setup on my github:  https://github.com/thiagoralves/defcon26
In there you will find the ladder logic programs for all 3 PLCs, the ScadaBR GUI, and the code for all the exploits.

About the parts you will need, here is the list:
1. Allen-Bradley Micrologix 1400 Series B
2. Schneider Modicon M221
3. OpenPLC (running on whatever platform you want. In this case I used the UniPi v1.0)
4. Arduino UNO boards (x2)
5. 24V Industrial I/O Arduino Shield:  https://www.rugged-circuits.com/24v-industrial/24v-industrial-shield (x1)
6. Portable imersion heater, like this one:  https://www.bedbathandbeyond.com/store/product/portable-immersion-heater/1011091717?skuId=11091717 (x3)
7. 24V relay (x1)
8. NTC 10K 3950 Temperature Sensor (x3) You can find it here:  https://www.amazon.com/gp/product/B0185P4MVO/ref=oh_aui_search_asin_title?ie=UTF8&psc=1


You will need the arduinos because neither the Allen-Bradley or the Schneider PLCs have analog inputs. So I connected the temperature sensors to each arduino board, and wrote a little program that converts the analog temperature into an 8-bit word that is sent using 8 pins in parallel. Then, you just connect these 8 pins to 8 digital inputs of the PLCs. Unfortunately, the Modicon PLC won't take 5V as a good input voltage source, so I had to use the 24V Industrial I/O Arduino shield on top of that for the Modicon to be able to read the 8 inputs.

After you get everything in place, just upload the codes to each PLC and setup the ScadaBR HMI. Let me know if you have questions on how to do that.
Reply 0 0
ericbaylor

Hello Thiago,

Thank you for the detailed list. I used it to order many of the items I didn't already have, so it was super helpful. I am starting the process of builiding it all now. I ran into a bit of a challenge getting RSLogix for the Allen-Bradley Micrologix 1400 Series B. I will continue working to get that but have shifted my focus to setting up the Unipi v1.1. I'll keep you updated as it progresses but just wanted to say thank you for the information.

Reply 0 0
Reply