Following requests from many users, the runtime v4 is now available for Windows with a native installer. You can download it from Autonomy’s website: https://autonomylogic.com/runtime
 
Happy 2026! 🎉
Reply 6 0
yaseralie
I downloaded and installed,
But I cant access the runtime from https://127.0.0.1:8443
How to open the runtime?
Now, I am still using runtime v3, using wsl on Windows
Reply 0 0
PeBi
Reply 1 0
yaseralie
Thank You,
I already tried this runtime v4.
It is great.
By the way, how about slave device concept in runtime v4?
Reply 0 0
thiagoralves
Reply 0 0
plcwill
I have similar problem with the slave with Razio or even Snap Trainer so I can test the modbus side. Have uploaded a program to the board Comfile 32TA ( Arduino Mega) which as haft is not controlled by modbus but, enabled Modbus RTU so I can see the first 8 input pins and the first 8 output pins and also the Analog pins. The question is do I need to have the runtime running when I uploaded the program to the board? I will try to find the above tread in the forums.
Reply 0 0
thiagoralves
No you don't. The runtime is the piece of software that RUNS your PLC program. You can have the runtime running on a PC, a Linux device, or an Arduino board (the runtime for Arduino boards is simplified, so some things are missing on it when compared with the Linux runtime for example). When you upload a PLC project to an Arduino board, the runtime goes with it.
 
The runtime running on your PC has nothing to do with the runtime running on the Arduino board. Essentially, each one is an individual PLC (PLC runtime running on PC/Linux, and PLC runtime running on Arduino board). However, you can connect two or more PLCs together by using Modbus for example, where the runtime on the PC will use Modbus to read/write data from the runtime on the Arduino board. Currently you can't connect an Uno board to the runtime v4 on a PC/Linux because the runtime v4 only supports Modbus TCP (over Ethernet), and the Uno only supports Modbus RTU (over Serial/USB). Once Modbus RTU lands on the runtime v4 you should be able to connect them as you could using v3 runtime. However, this connection is not necessary. People just connect multiple PLCs together when they are building large projects or when they are using PLCs as remote IOs. You can run your PLC code independently on the Arduino board.
Reply 0 0
plcwill
I understand what you are talking about but, my goal is to see these inputs via modbus and be able to control these outputs as well. What modbus addresses do live at? Or, does this mean I may need to add my own custom modbus code in C/CC+ into this program?
Reply 0 0
thiagoralves
Tick Modbus RTU on the device configuration screen with your Arduino Uno selected and upload your program to it. That's it. Modbus mapping goes on your located variables where:
 - %QX locations map to Modbus Coils (%QX0.0 = Coil 0)
 - %IX locations map to Modbus Input Status (%IX0.0 = Input 0)
 - %QW locations map to Modbus Holding Registers (%QW0 = Holding Register 0)
 - %IW locations map to Modbus Input Registers (%IW0 = Input Register 0)
Reply 0 0
plcwill
Tick Modbus RTU on the device configuration screen with your Arduino Uno selected and upload your program to it. That's it. Modbus mapping goes on your located variables where:
 - %QX locations map to Modbus Coils (%QX0.0 = Coil 0)
 - %IX locations map to Modbus Input Status (%IX0.0 = Input 0)
 - %QW locations map to Modbus Holding Registers (%QW0 = Holding Register 0)
 - %IW locations map to Modbus Input Registers (%IW0 = Input Register 0)
That's what I did when uploaded the program the first time on COM4 and I didn't see any values. The board is Comfile 3TA which is an Arduino Mega not a Uno. But, that doesn't matter. I will have to try again with the simulator and let you what I find. I had feeling that you didn't change this for Ver3 to Ver4.
Reply 0 0
thiagoralves
What values are you expecting to see? Are you getting any connection errors? Is your program running on your board (successful compilation and upload)?
Reply 0 0
plcwill
What values are you expecting to see? Are you getting any connection errors? Is your program running on your board (successful compilation and upload)?
It uploads fine. It also connects fine to Razio on COM4 through the upload port but , I don't see any values even the Analog values. I attached the project for you to test. The final project will use Serial3 which is the RS485 port. I need to see values on pins 22 - 29 (inputs) and pins 38 -45(outputs). I could try Serial0 or Serial1 to test on.
Reply 0 0
thiagoralves
Have you defined those pins on your project’s pin mapping? If you don’t map any pins, they won’t be available on Modbus.
Reply 0 0
plcwill
Have you defined those pins on your project’s pin mapping? If you don’t map any pins, they won’t be available on Modbus.
I got it working. I defined those pins when I started this project but, I took them out thinking that the new version would make the rest of the un-defined pins modbus.
 
BTW, I would love to add the Comfile 32TA (Arduino Mega) and 18TA (Arduino Uno) to the list of boards. Comfile has a new modular Arduino Industrial that similar Automation Direct's Arduino controller
Reply 0 0
corydoras
The OpenPLC Editor V4.1.1 is FANTASTIC!!!! Have tried it now on ESP32, and it just works, debug and all. Thanks to @ThiagoAlves and the team for ALL the effort. Looking forward to lots of lab projects with this. Again THANK YOU!!!
Best reg
Roy
Reply 1 0