hjbleier
Hi,

I am using the PiXtend V2 -S-. I found out that the Output coil mapping is a bit different from the picture you did on PiXtend runtime page for V1. The V2-S- board uses %QX0.0-%QX0.3 for the 4 triacs (DO-0 thru DO-3) and %QX0.4-%QX0.7 for the 4 relays (Relay-0 thru Relay-3).

Anyways I got to do some seal-in virtual relays for my project for the logic to work correctly. So my question is where should I start my virtual relay addresses? %QX1.0? Also what is the limits when using the PiXtend hardware layer driver? What is the full range of modbus addresses available to use?

Thanks,
Howard B.
Reply 0 0
thiagoralves
Hi there! The limits are not defined by the hardware layer you’re using. It is defined by the size of the buffer inside OpenPLC. The size of the coils buffer is 8192, so it goes up to %QX1023.99
Reply 0 0
Reply