Hello...
I'm new in OpenPlc. Years ago I do pretty big project with Proview.se package. It was really step learning curve, and I allready forgot how to do job on it.
I hope that OpenPlc is not so demanding, but as I understand this is SoftPlc only. ( Proview.se is softPLC with HMI). So for HMI I need to chose SCADA package compatible with OpenPLC.  I do search the web and there are SCADABR and SCADA-LTS. But both of them seems pretty old. There are years from last update (or I check wrong place).
So what HMI is recommended for OpenPLC.
I wish to have visible switches, tanks, conveyors in HMI. Probably animated.
Is it possible to do that with OpenPLC/HMI, or is better to stuck with Proview.se.
 
Thanks for any help.
Reply 0 0
thiagoralves
ScadaBR is probably the best open source HMI you can get. It still gets updates, but in a slower pace. You can get the latest release here: https://github.com/ScadaBR/ScadaBR/releases/tag/v1.2
 
I've made a video showing how to connect OpenPLC runtime with ScadaBR. You can check it out here:  https://youtu.be/KrcL6lhAHKw?si=q2RCqxVmxqfcDBGo
 
OpenPLC will work with any HMI that talks Modbus RTU or Modbus TCP, which is virtually all of them. I haven't seen an HMI solution that doesn't support Modbus yet. For commercial HMIs, Ignition is one of the best and most used ones. It also works with OpenPLC through the Modbus connector.
Reply 0 0
eslavko
So the SCADABR is "probably" the best choice even if it's last updated in Sept 15. 2021? That's scare me that they will possible have some installation problem in year or two (if not already). I looking for something with long term support and of course to be free. As I already wrote that I make some automation ob big farm decade ago and now they want some additional updates. I did ask developers of proview.se how to update to current version and they told me that I need to install every version they have as they guarantee that every new version is compatible with previous but not with older. And they have proview versions bonded with OS versions. In short if I want to update system from version I have to current that means I need to go with 18 versions of proview and 6 versions of OS. I did try but each versions seems to took at least 4-5 hours (mostly waiting) to be done.  And proview is really hard to use, and in years I forgot near everything I learned.
Reply 0 0
thiagoralves
Honestly, stick with ScadaBR. It’s been around for years (I would say about 15 years at least), is Java based (which means it will work forever), and it is quite simple to use. I took a look at Proview and gave up on using that for the same reasons you mentioned. ScadaBR is a snap compared to that experience.
Reply 0 0
eslavko
Still checking if suit job. I need to refresh farm installation. Basically there are around 10 PLCs and are basically just IO with modbusRTU. Some of them have little more than just IO to be safe in case when modbus connection fail. So near all job is done by proview. The exception is cogeneration PLC wich do near all job and have just parameters set over modbus, and have processor not compatible with arduino. As for now seems that Im stuck on C to write/modify all IO-PLC s. And for main unit (running on PC) I can use OpenPLC. 
Reply 0 0
thiagoralves
You can use OpenPLC Runtime on an Industrial PC or an Industrial Raspberry Pi (we have an awesome one being sold in our store by the way: https://autonomylogic.com/product/sl-rp4/ 😉 and then attach all the 10 Modbus RTU remotes to it as slave devices. Then you do all your logic in OpenPLC and then use ScadaBR to visualize it. Easy. Done.
Reply 0 0
eslavko
Keeping remote PLCs as is this seems good solution. The cons are that remote PLCs use some "werid" language hard to be used for someone else.
Using raspberry  instead PC seems good solution to reduce power and aren't bulky.
Bur running SCADABR in same raspberry I'm afraid is not god option. At least as I want history chart the data must be stored somewhere. And SD cards aren't good solution to have database on them. Using pen drive isn't advantage too. So what others use for storage? USB harddrive?
In current setup I have all data stored in harddrive and in last decade I fill near 2TB of space. I know that actually I need maybe 2% of data to be stored in such long period and rest just take space. So in new system I should somehow manage storage time based on data type.
Reply 0 0
thiagoralves
Ideally the raspberry should be used only for the OpenPLC runtime. Adding SCADA to that will most certainly ruin the lifespan of the SD card. You can run ScadaBR on any Windows or Linux box available, or in a server (ideally). Just make sure you isolate the IT (web portal) and OT (modbus) networks for security reasons.
Reply 1 0
leo2089
You cal also install scada LTS on a linux machine. You can use debian 12 no gui in a vm it works perfectly.
Reply 1 0